This is the html version of the file http://files.engineering.com/download.aspx?folder=5b022082-151c-41d4-af4c-06845b308475&file=NETA_ct-testing_Good.pdf. Google automatically generates html versions of documents as we crawl the web.
Tip: To quickly find your search term on this page, press Ctrl+F or ⌘-F (Mac) and use the find bar.
Back to the Basics — Current Transformer Testing
Page 1
Fall–Winter 2004
1
As test equipment becomes more sophisticated with better features
and accuracy, we risk turning our field personnel into test-set opera-
tors instead of skilled field service technicians. A test-set operator
connects the leads, pushes the buttons, and records the results, hoping
the numbers he records are good. A test technician connects the leads,
pushes the buttons, and records the results. However, the test technician
understands what the test set was doing while all the lights were flash-
ing, and why. The technician can also evaluate the results and determine
if a retest is necessary with different connections or substitute external
equipment for tests when the test equipment malfunctions. The purpose of
this article is to help a test-set operator understand the tests he performs,
reinforce a test technique, or add it to his repertoire.
Description of Operation
During normal operation, a current transformer (CT) transforms higher
current into a more manageable secondary current. This transformation
is made possible by copper coils wrapped around an iron core, with the
ratio between primary and secondary currents determined by the ratio
between the number of primary and secondary turns. Bar- and window-
type CTs do not have a physical primary winding and are considered to
have one primary turn. When current flows through the primary winding,
the following actions occur:
• The iron core inside the transformer is magnetized.
• The magnetic field in the iron core induces a voltage in the sec-
ondary coils.
• If the secondary circuit is closed, a current flows through the
secondary circuit in proportion to the CT ratio.
The current transformation requires a small amount of energy to mag-
netize the iron core that creates small energy losses such as eddy currents,
and heat caused by current flowing through the windings. Therefore, the
secondary current is not a perfect representation of the primary current.
All CTs that are built to ANSI standards have an accuracy class to outline
what effect the losses have on the secondary current under normal con-
Back to the Basics —
Current Transformer Testing
Chris Werstiuk
Valence USA
The Official Publication of the InterNational Electrical Testing Association
Fall – Winter 2004
Valenceusa@earthlink.net
www.home.earthlink.net/~valenceusa/
neta@netaworld.org
www.netaworld.org
Reprinted with permission of the InterNational
Electrical Testing Association. Copyright 2004.
All rights reserved.
ditions. The accuracy class is the
minimum accuracy guaranteed by
the manufacturer, although the CT
may be built to higher standards.
Like every other transformer,
CTs can only transform a finite
amount of energy. This is usu-
ally the voltampere rating for
normal transformers. The CTs
energy limitation is included in
the accuracy class but is shown as
a maximum burden. The CT bur-
den is the amount of impedance
(ac resistance) connected to the CT
secondaries and is usually rated in

Page 2
2
NETA WORLD
Fall
ohms or volts. The manufacturer only guarantees CT
accuracy up to a maximum burden rating, and CT
performance will degrade if the secondary burden is
larger than rated.
Visual and Mechanical Inspections
Equipment Specifications
While performing visual and mechanical inspec-
tions, always compare equipment nameplate data
with drawings and specifications. Every CT test sheet
should include the following information:
Serial Number (when possible): The serial number
is important to organize test results and allow a refer-
ence when comparing test results to manufacturer’s
specifications. The serial number can also be used
when ordering replacement or new CTs from manu-
facturers.
Model Number (when possible): The model
number is important when comparing test results to
manufacturer’s literature and ordering replacement,
new, or spare CTs from manufacturers.
Ratio: The CT ratio is the most important piece of
information regarding the CT and must be recorded
from the nameplate or the design criteria. The ratio
determines the CT’s operating characteristics and is
used as reference for tests. If the CT has multiple taps
(different possible ratio combinations), all taps should
be recorded for future reference in case a new ratio is
required for the application. This will allow a review
of the options without visiting the site beforehand.
Accuracy Class: The CT accuracy class comprises
a number-letter-number combination and indicates
the CT’s ability to perform accurately under differ-
ent conditions. In other words, the CT accuracy class
indicates the CT’s performance characteristics and the
maximum burden allowable on the CT secondaries.
CTs can be separated into two distinct groups: meter-
ing and protection or relay. A CT can have ratings for
both groups. See Figure 1 for a list of typical accuracy
classes.
The CT accuracy class is made up of three parts,
which are described in conjuction with Figure 2.
Accuracy: The first number in the CT accuracy class
is the rated ratio accuracy in percent. For example, the
ratio of a 0.3B0.1 metering-class CT is accurate within
0.3 percent as long as the CT burden rating is not ex-
ceeded. The ratio of a 2.5C100 protection-class CT is
accurate within 2.5 percent if the CT burden rating is
not exceeded.
Current-Transformer Class: The second part of the
accuracy class is a letter. The letter distinguishes for
what application the CT is rated. A CT can have dual
ratings and be used in metering or protection applica-
tions, if both ratings are listed on the nameplate.
Metering-class CTs have the letter B in the accuracy-
class rating. They are designed for maximum accuracy
from very low currents to the maximum CT rating.
These CTs are often used to record power consumption
and are the basis for electrical bills, hence the need for
accuracy. A typical metering-class CT has an accuracy
class similar to 0.3B0.1
Protection-class CTs have the letters C, H, L, or T
to indicate the protection-class rating.
• A C-rating indicates that the CT accuracy can be
calculated before construction because there is no
appreciable leakage flux in the CT design.
• A T-rating indicates that the CT can have significant
leakage flux, and the CT accuracy must be obtained
by testing in the factory.
• An H-rating indicates that the CT accuracy rating
is applicable within the entire range of secondary
currents from five to 20 times the nominal CT rating.
These are typically wound CTs.
• An L-rating indicates that the CT accuracy applies
at the maximum-rated secondary burden at 20 times
rated only. The ratio accuracy can be up to four
Figure 1a — CT Accuracy Classes and Correction Factors
Figure 1b — CT Accuracy Classes and Correction Factors
CORRECTION FACTOR LIMITS FOR CTs
ACCURACY
100% RATED CURRENT
10% RATED CURRENT
CLASS
MIN
MAX
MIN
MAX
1.2
0.998
1.012
0.976
1.024
0.6
0.994
1.006
0.988
1.012
0.3
0.997
1.003
0.994
1.006
0.5
0.995
1.005
0.995
1.005
STANDARD BURDENS FOR STANDARD 5-AMP / 60 Hz
SECONDARY CURRENT TRANSFORMERS
BURDEN
DESIGNATION
STANDARD SECONDARY BURDEN RATINGS
IMPEDANCE
OHMS
VOLT AMPS
(VA)
POWER
FACTOR
B-0.1
0.1
2.5
0.9
B-0.2
0.2
5
0.9
B-0.5
0.5
12.5
0.9
B-1
1
25
0.5
B-2
2
50
0.5
B-4
4
100
0.5
B-8
8
200
0.5

Page 3
LD
Fall–Winter 2004
3
METERING CLASS
0.3 B 0.3
ACCURACY IN PERCENT (%)
MAXIMUM BURDEN IN OHMS (0.3 Ohms)
CT CLASS – “B” = METERING
PROTECTION CLASS
2.5 C 100
ACCURACY IN PERCENT (%)
MAXIMUM BURDEN IN VOLTS @ 20* CT AMP RATING (100A)
MAXIMUM OHMS = BURDEN/100 = 100/100 = 1.0 OHMS
CT CLASS
“C” = DONUT CT WITH CALCULATED % ACCURACY
“T” = % ACCURACY TESTED IN FACTORY
“H” = ACCURACY APPLIES UP TO 20x CT NOMINAL AMPS
“L” = ACCURACY CAN VARY UP TO 4x RATING DEPENDING ON LOAD
times greater than the listed val-
ue, depending on the connected
burden and fault current. These
are typically window, bushing,
or bar-type CTs.
Protection-class CTs are not as
accurate as metering-class CTs
but are designed to operate over a
wider range of current. This wider
range is necessary to allow the
protective relay to operate at dif-
ferent fault levels. Protection-class
CTs are typically rated to operate
accurately up to 20 times the CT
rating. A typical protection-class
CT has an accuracy class similar
to 2.5C100.
Burden: The third part of the
accuracy-class rating follows the
letter and indicates the maximum
burden allowed. If the CT second-
ary-burden rating is exceeded, CT
accuracy is not guaranteed.
Metering-class CT burdens are
displayed as secondary ohms. For
example, the ratio of a 0.3B0.1 rated
CT is accurate to 0.3 percent if the
connected secondary burden im-
pedance does not exceed 0.1 ohms.
A 0.6B8 rated metering-class CT
will operate within 0.6 percent
accuracy if the secondary burden
does not exceed 8.0 ohms.
Protection-class CT burdens are
displayed as the maximum sec-
ondary volts allowable if 20 times
(100 amperes with a five-ampere
nominal CT secondary) the CT
rating were to flow through the
secondary circuit. For example,
a 2.5C100 protection-class CT is
accurate within 2.5 percent if the
secondary burden is less than 1.0
ohm (100 volts / 100 amperes).
CT Type: The four typical CT
types include window, bushing,
bar, and wound.
• Window CTs are the most com-
mon. They are constructed with
no primary winding and are in-
stalled around the primary con-
ductor. The electric field created
by current flowing through the
conductor interacts with the CT
Figure 2 — Understanding CT Ratings
core to transform the current to the appropriate secondary output.
Window CTs can be of solid or split core construction. The primary
conductor must be disconnected when installing solid window CTs.
However, split core CTs can be installed around the primary conductor
without disconnecting the primary conductor.
• Bushing CTs are window CTs specially constructed to fit around a
bushing. Usually they cannot be accessed, and their nameplates are
found on the transformer or circuit-breaker control cabinets.
• Bar-type CTs operate on the same principle of window CTs but have
a permanent bar installed as a primary conductor.
• Wound CTs have a primary and secondary winding like a normal
transformer. These CTs are rare and are usually used at very low ratios
and currents, typically in CT secondary circuits to compensate for low
currents, to match different CT ratios in summing applications, or to
isolate different CT circuits. Wound CTs have very high burdens, and
special attention to the source CT burden should be applied when
wound CTs are used.
Voltage Class: The CT voltage class determines the maximum volt-
age with which a CT can be in direct contact. For example, a 600-volt
window CT cannot be installed on or around a bare 2400-volt conductor.
However, a 600-volt window CT can be installed around a 2400-volt cable
if the CT is installed around the insulated portion of the cable and the
insulation is rated correctly.
Physical and Mechanical Condition
Verify the physical and mechanical condition of the CT. When pos-
sible, the CT should be inspected for shipping damage, incorrect bracing,
cracks, and general overall condition. The CT should be permanently
mounted and not supported by the primary conductor.
Correct Connection of Transformers
Verify the correct connection of transformers with system require-
ments. This step is often the most critical step performed. Incorrect CT
connections can cause significant problems on any polarity-sensitive
metering or protection scheme such as generator protection (IEEE 32,

Page 4
4
NETA WORLD
Fall
40, 67), line protection (IEEE 21, 67, 78), or differential
elements (IEEE 87). In many instances, the connection
is as important as the CT polarity. If the primary polar-
ity of a CT is reversed, the secondary wiring can also
be reversed to achieve the desired overall polarity.
Two wrongs often make a right when working with
CT connections.
Adequate Clearances
Verify that adequate clearances exist between
primary and secondary circuit wiring. Inspect the
space between the CT phases, ground, and second-
ary conductor to ensure adequate clearance. (Quick
rule-of-thumb: one inch per kilovolt plus one inch.)
Remember that line-to-line voltages apply between
phases. Also check that the secondary wiring is not
run parallel and/or close to the primary conductor
to prevent any current from being induced into the
secondary path. All wiring above the primary con-
ductor should be permanently affixed to the structure
to prevent the wiring from falling onto the primary
conductors in the future. (Sticky backs are not consid-
ered permanent.)
Grounding and Shorting Connection
Verify that all required grounding and shorting
connections provide contact. CTs are always shipped
with shorting devices installed if the burden circuit
cannot be completed at the factory. Measure the re-
sistance between both sides of the terminal block to
ground before removing the shorting device to ensure
the device is operating correctly. The measured resis-
tance should be negligible. The CTs should remain
shorted until the secondary wiring is complete and
loop-tested. Always check to ensure that the short-
ing devices are removed on in-service CTs just prior
to energization.
CT Electrical Tests
Insulation-Resistance Test
In accordance with NETA specifications, “Perform
insulation-resistance tests to ground of the CT and
wiring at 1000 volts dc. For units with solid-state com-
ponents, follow manufacturer’s recommendations.
When applicable, perform insulation-resistance
and dielectric-withstand tests on the primary wind-
ing with the secondary grounded. Use test voltages
in accordance with Tables 100.5 and 100.9 respectively
in the NETA specifications.”
When electromechanical relays were king, insula-
tion-resistance tests of CTs and wiring were an ac-
ceptable method of testing the entire circuit including
the internal relay wiring. In the age of microprocessor
relays, the risk of damage to the new, more sensitive,
relays must be weighed against the benefit of the test.
I recommend isolating the CTs from the external wir-
ing at the first terminal block or test point and apply-
ing the test voltage between the CT and ground. All
three CTs can be tested simultaneously. Investigate
any measurement below 100 megohms.
Never perform this test on bushing CTs while the
power transformer is under vacuum. Although a
perfect vacuum is a perfect insulator, the transformer
vacuum is not perfect, and there is a strong possibility
of causing a flashover inside the transformer.
Polarity Test
Perform a polarity test of each current transformer.
There are two generally accepted methods of testing a
CT’s polarity using simple meters and connections:
DC Kick/Flick Test: This is the tried and true meth-
od for testing CT polarity, used before electricity
was discovered by some accounts. For this test, a
dc battery, a dc voltmeter or ammeter (preferably
analog), and test leads are required. This method
is a quick and easy test for polarity, but there is a
possibility that it may leave remnant flux in the
CT. Remnant flux may cause saturation when the
CT is next energized. (See C57.13.1, paragraph 4.3.)
Always perform an excitation/saturation test after
performing this test. The steps of the dc kick/flick
test are as follows:
1. Connect the positive of the voltmeter to the H1
(marked) terminal of the high-voltage side of the
CT and the negative lead to the H2 as shown in
Figure 3.
Figure 3 — DC Polarity Test Circuit Window Type CT
12V
+
-
H1
H2
X2
PRIMARY
CONDUCTOR
V
10V SCALE
12V / (10/5) = 6 V
+
-
TEST
LEAD
PRIMARY
CONDUCTOR
TEST
LEAD
X1
10:5 A CT

Page 5
LD
Fall–Winter 2004
5
• If testing a window-type CT, run a wire through the
CT and connect your meter across the wire. Make
note of the wire and meter polarity.
• If the CT is enclosed within a breaker, close the
breaker and connect your voltmeter across the
breaker poles. Review the CT drawing carefully
and note the CT polarity and meter polarity.
• If the CT is enclosed within a generator, connect the
voltmeter across the generator windings. Review
the CT drawing carefully and note the CT polarity
and meter polarity. If the star point is not accessible,
connect the voltmeter across two generator leads
and short the remaining generator lead to one of
the generator leads under test.
• If the CT is enclosed within a transformer, connect
the voltmeter across the transformer bushings asso-
ciated with the CT and short the remaining bushing
to the nonpolarity bushing under test. Review the
CT drawing carefully and note the CT polarity and
meter polarity. (See Figure 4.)
3. Connect the negative terminal of the battery to the
nonpolarity of the CT winding under test. Momen-
tarily touch or connect the battery’s positive termi-
nal to the polarity terminal of the CT winding under
test.
4. Closely watch the needle or analog scale of the
voltmeter. It should jump in the positive direction.
This happens in a fraction of a second, so the meter
must be monitored very closely. If the voltmeter
kicks in the positive direction, the polarity marks
are correct. If it kicks in the negative direction, the
polarity marks are incorrect.
AC Voltage Method: This method digs deep into
transformer theory and can be used with any kind of
transformer. Most transformer polarities are marked
with additive polarity that allows creation of an au-
totransformer by connecting X1 and H2 or H1 and
X2 together.
This method is limited by the accuracy of the meters
and may not be reliable with unstable source voltages
(such as construction power or generator) and high
ratio CTs due to the low H side voltages induced.
To test polarity using ac voltage, a variable trans-
former and voltmeter (preferably two) are required.
Use the following steps to test for CT polarity using
the ac method, as shown in Figure 5.
Figure 4 — DC Polarity Test Circuit Delta Connected Generator
V
0.1V SCALE
+
-
TEST
LEAD
H
1
X
1
X
2
12V
+ -
X2
X1
TEST
LEAD
R
S
T
DELTA CONNECTED
GENERATOR
TEST
LEAD
2000:5 CT
12V / (2000/5) = 0.03V
Figure 5 — AC Voltage Ratio Test Circuit
H1
H2
X2
PRIMARY
CONDUCTOR
PRIMARY
CONDUCTOR
TEST
LEAD
X1
15:5 A CT
AC VARIAC = 15V
V
AC
V
RATIO TEST
VM2 = [VM1/CT ratio]
VM2 = 15V / (15/5)
VM2 = 5V
VM1
VM2
V
VM3
POLARITY TEST
VM3 = VM1 + VM2
VM3 = 15V + 5V
VM3 = 20V
2. Calculate the expected voltage using the battery
voltage and the CT ratio. (Battery voltage/CT
ratio.)
1. Connect a variable transformer (such as a Variac)
across the secondary winding of the CT.
2. Connect a voltmeter (VM1) across the secondary
CT winding and variable transformer.
3. Connect a jumper between the nonpolarity of the
H winding and the polarity of the X winding.
4. Connect a voltmeter (VM3) from the polarity mark
of the H winding to the nonpolarity mark of the X
winding.

Page 6
6
NETA WORLD
Fall
5. Increase the variable-transformer test voltage to a
predetermined value. Calculate the expected value.
([VM1 / CT ratio] + [VM1]). If VM3 displays the
expected result, the CT polarity markings are cor-
rect. If VM3 is less than VM1, the test connection or
the CT polarity markings are incorrect. (Note: VM1
and VM3 can be one voltmeter switching between
positions if the test voltage remains stable.)
Ratio-Verification Test
The NETA specifications state, “Perform a ratio-
verification test using the voltage or current method
in accordance with ANSI C57.13.1 (IEEE Guide for
Field-Testing of Relaying Current Transformers).” The
CT ratio test determines the CT accuracy, and the re-
sults should be compared to the accuracy class. The
easiest and most accurate CT ratio test method for
most applications is the voltage method and is the
method we will discuss here.
It may seem strange to use voltage to test a CT ratio,
but basic transformer theory applies to all transform-
ers, including CTs. One of the first transformer funda-
mentals is that the transformer ratio applies inversely
to current and voltage. A 400:5 CT ratio will convert
400 primary amperes to five secondary amperes and
convert 80 secondary volts to one primary volt. We
apply this principle to CT testing because it is easier
to locate, carry, and apply an 80-volt voltage source
than a 400-ampere current supply. The voltage method
is also more accurate because measurements can be
made directly instead of applying CTs and clip-on am-
meters that add error based on their accuracy. The
applied voltage must be well below the saturation
voltage or there will be a significant error reported.
The steps for a ratio-verification test are as follows:
1. Connect a voltage source (variable transformer) and
voltmeter (VM1) across the CT secondary, as shown
in Figure 5.
2. Connect a voltmeter (VM2) across the CT primary.
3. Apply a voltage to the CT secondary and measure
the secondary (VM1) and primary voltages (VM2)
simultaneously. Calculate the ratio between the two
voltages (VM1 / VM2).
This voltage should match the CT ratio (primary /
secondary). You can repeat the procedure above for
each tap of a multitap CT, but I prefer to treat the CT
taps as I would an autotransformer. I apply a voltage
across the maximum ratio tap and measure all remain-
ing taps to a common point, as shown in Figure 6.
Prove all tap combinations by using the information
recorded from this test.
Excitation Test
In accordance with NETA specifications, “Perform
an excitation test on transformers used for relaying
applications in accordance with ANSI C57.13.1. (IEEE
Guide for Field Testing of Relaying Current Transformers).”
During normal operation, the CT operates as a nearly
perfect machine with very small energy losses neces-
sary for CT operation. The magnetic theory involved
in transformer operation is too complex to address in
this article, but the magnetic circuit can be compared to
a normal electrical circuit: the primary winding (gen-
erator), iron core (transmission line), and secondary
winding (load). During normal CT operation the high-
side winding (generator) supplies energy through the
iron core (transmission line) to the low-side winding
(load) with small losses in the transmission line.
When a CT is saturated, the magnetic path inside
the CT operates like a short circuit on the transmis-
sion line. Almost all of the energy supplied by the
primary winding is shunted away from the secondary
winding and is used to create a magnetic field inside
the CT. Saturated CTs can be very deceiving when
used to supply protective relays as they may operate
normally at low current levels and not operate at all
during fault currents.
Some of the following conditions can cause CT
saturation:
• CT secondary burden greater than rated.
• Extremely high current flowing through the CT
(fault current).
• Current flowing through CT primaries with open-
circuit secondaries.
• DC current flowing through either winding.
The excitation test is used to prove that the CT is not
saturated and will operate within specifications at the
rated burden. It is important to remember when com-
paring test results to the burden rating that the burden
V
H1
H2
X1 X2
V
AC
VM2 = 0.5V
X3 X4 X5
X2-X3 = 100:5
X1-X2 = 200:5
X1-X3 = 300:5
X3-X4 = 400:5
X4-X5 = 500:5
X2-X4 = 600:5
X1-X4 = 800:5
X3-X5 = 900:5
X2-X5 = 1000:5
X1-X5 = 1200:5
TEST 1 =
X1-X5 TO VM2
V
TEST 2 = X2-X5
RATIO TESTS 2-4
V
VM1 = 120V
V
TEST 3 = X3-X5
V TEST 4 = X4-X5
TEST 2 = VM1 * (TEST RATIO) / (FULL RATIO)
TEST 2 = 120 * 1000 / 1200
TEST 2 = 100 V
TEST 3 = VM1 * (TEST RATIO) / (FULL RATIO)
TEST 3 = 120 * 900 / 1200
TEST 3 = 90 V
TEST 4 = VM1 * (TEST RATIO) / (FULL RATIO)
TEST 4 = 120 * 500 / 1200
TEST 4 = 50 V
RATIO TEST 1 = X1-X5 TO VM2
VM2 = VM1 / CT RATIO
VM2 = 120 / 240
VM2 = 0.5V
POLARITY TEST 1
VM3 = VM1 + VM2
VM3 = 120 + 0.5
VM3 = 120.5V
Figure 6 — Multi Ratio CT AC Ratio CT Test Connections

Page 7
LD
Fall–Winter 2004
7
rating is a minimum value. The CT
could actually have a higher rat-
ing. This happens often in trans-
former bushing applications.
A saturation test is performed
by applying ac voltage to the CT
secondary and increasing the volt-
age in steps until the CT is in satu-
ration. The test voltage is slowly
decreased to zero to demagnetize
the CT. The test results are plot-
ted on a logarithmic graph and
evaluated based on the transition
period between normal operation
and saturation. This transition is
called the knee of the curve and
is directly related to the voltage
burden rating of the CT. Use the
following steps to perform an ex-
citation test:
1. Obtain the CT accuracy class.
2. Convert the accuracy class to a voltage burden rat-
ing. (See Part I of this article Fall 2004 issue of NETA
World.)
3. Connect the test equipment per Figure 7 to the first
CT scheduled for test.
4. Slowly increase the voltage until saturation. (We
will use 1000 milliamperes for this article, but
saturation could be higher or lower depending on
CT construction.) Watch the current and note the
voltage where the current increase beginsto increase
dramatically. Note the voltage where the current
reaches 1000 milliampere.
Figure 7 — Excitation Test Connection
H1
H2
X2
PRIMARY
CONDUCTOR
PRIMARY
CONDUCTOR
X1
AC VARIAC
V
AC
VM1
800+ VOLTS AS
PER CT RATING
A AM1
TYPICAL MAX = 1000mA
CT RATING
2.5C800
5. Slowly decrease the voltage to zero.
6. Determine your test voltages using four equal steps
to the first-noted voltage and six equal steps be-
tween the first-noted voltage and the second-noted
voltage at 1.0 amperes.
7. Repeat the test using the voltage points determined
in Steps 4 and 6 and record the milliamperes at each
step. Never decrease the voltage until the maximum
test voltage is reached. You must either skip the
voltage step or restart the test from 0 volts if the
voltage must be decreased to record a result.
8. Slowly decrease the voltage to zero volts. If the
voltage is turned off for any reason before the
test is complete, the CT may remain saturated.
To desaturate the CT, increase the voltage to 1000
milliamperes (saturation) and slowly decrease the
voltage to zero.
9. Graph the results on a log-log graph and compare
to the manufacturer’s supplied results. See Figure
8 to help evaluate the results.
Manufacturer’s results are often typical for a class
of CT, although each CT may not have been tested.
Because every CT has different operating character-
istics, the results may not be exactly the same. Look
for similarities and glaringly obvious differences
when evaluating the results. If manufacturer’s re-
sults are not available, the knee of the curve must
be higher than the rated burden voltage.
10. Repeat the test using the same test voltages for all
CTs of the same rating. Start from the beginning
for CTs with another rating.
Determining Total Burden
Measure current circuit burdens at transformer
terminals and determine the total burden. This test
is very important and often missed in today’s world
Figure 8 — Example Excitation Test Results
CT SATURATION CURVE
10
100
1000
10
100
1000
10000
CURRENT (milliAmps)
V
O
L
T
S
(V
)
PHASE A
PHASE B
PHASE C
NORMAL OPERATING REGION WITH A
LINEAR RELATIONSHIP BETWEEN
VOLTAGE AND CURRENT
"KNEE" TRANSITION POINT BETWEEN
NORMAL OPERATION AND SATURATED
REGION - MUST BE ABOVE CT BURDEN RATING
CT BURDEN
RATING "L400"
CT SATURATION

Page 8
8
NETA WORLD
of fast track projects where the testing is broken into
stages or multiple testing companies are used in dif-
ferent parts of the project. This test is the final-proof
test used to ensure that:
• CTs are not energized with shorting devices in-
stalled if used for metering or protection.
• CTs are not left open circuit if not used.
• CTs are connected with a single ground point.
• CT burden ratings are not exceeded.
• All connections are tight.
There are many ways of performing this test, each
with its own merits and pitfalls, but this article is fo-
cused on the basics and will only cover the voltage-
drop method. It is time-consuming but only requires
a voltage/current source and a voltmeter. The test
applies five amperes through the secondary circuit
with a known ground reference while measuring the
voltage drop at each point of the circuit to ground.
Ohm’s law plus the measure of the voltage drop at
the source will give us the burden impedance. Analyz-
ing the voltage-drop patterns throughout the circuit
confirms the wiring is correct.
After all CT testing and secondary circuit wiring is
complete, follow the next steps to perform a second-
ary-loop test via the voltage-drop method.
1. Remove the CT secondary shorting devices and re-
move the ground from the circuit. Every CT circuit
should be grounded at one point only and have its
own path to ground per IEEE standard C57.13.2.
Many manufacturers incorrectly daisy chain all CT
grounds together contrary to this standard.
2. Connect an ac source between the CT secondary
feeder as close to the CT as possible and ground.
Slowly increase the voltage or current dial. A lamp-
ing kit may be used as the source. (A lamping kit is
a 120 volt ac source with a light bulb in series.) No
current should flow and light bulb remains off. If
current flows, a second ground exists somewhere
in the circuit which must be permanently removed.
Investigate possible sources of ground and repeat
this step until no current flows.
3. Connect a temporary ground between the neutral
of the test source and the CT star point. Increase the
source voltage until five amperes flow in the circuit.
If no current flows, the ground is incorrectly applied
or the circuit is incomplete.
4. Measure the voltage between the first CT circuit
terminal and ground. Multiply this number by the
measured current to obtain the voltampere burden
(VA = Volts * Amperes). Divide the voltage by the
current to determine the burden in ohms (Ohms =
Volts / Amperes). Check the CT rating to ensure
the burden is less than the nameplate value.
5. Measure the voltage between ground and every
connection. The voltage should drop incrementally
as you work through the circuit. Any increase in
voltage should be immediately investigated. The
most common problems found are:
• Unstable source voltages.
• Reverse polarity connections.
• Assumptions about what the terminal point
should be instead of using drawing references.
• Assumptions about where the terminal point is
instead of reading the designation.
6. Repeat Steps 2 through 5 for the other two CT
phases. The measured voltage patterns should be
similar to the other two phases in the circuit if they
are identical. Drastic deviations from the voltage
pattern should be investigated for loose connections
or shorts (e.g., single copper strand accidentally
connected between terminals). Additional devices
in one phase will cause higher voltages, but the
difference between devices should be consistent
between phases.
7. After all testing has been satisfactorily completed,
turn the ac source off and remove all test leads.
Reconnect the CT ground and check with an ohm-
meter after it is installed. Record the circuit burdens
on your test sheet.
Conclusion
Although the sophisticated test equipment of
modern test technicians makes all of our lives easier,
we often forget that the technicians before us were
frequently limited to a lantern battery, variable trans-
former, multimeter, and their imaginations. We can
use their example to complete the job when our test
set malfunctions or is damaged.
Reference
NETA 2001 Maintenance Testing Specifications for
Electrical Power Distribution Equipment and Systems
Chris Werstiuk graduated from the Electrical Engineering Tech-
nology program at the Northern Alberta Institute of Technology
and is a Registered Engineering Technologist and Journeyman
Power System Electrician. He has performed low-, medium-, and
high-voltage acceptance testing, commissioning, and maintenance
testing at various locations throughout the Americas. His experi-
ence is varied, and he is comfortable in mining, utility, generat-
ing, distribution, production, institutional, plant, pipeline, and
commercial environments. Chris is currently a Project Manager
for Valence USA, a full service field service and electrical training
organization.